Power-frequency withstand voltage (AC) 39kV/5minno breakdown, no flashover
Partial discharge 15kV≤10pC
Impulse voltage 95kV (10 times each positive and negative polarity)no breakdown, no flashover
Constant-voltage load cycle test in air (22kV, 95°C~100°C, each cycle heating 5h, cooling 3h, 30 cycles in total)no breakdown, no flashover
Constant-voltage load cycle test in water (22kV, 95°C~100°C, each cycle heating 5h, cooling 3h, 30 cycles in total)no breakdown, no flashover
Power-frequency withstand voltage (AC) 117kV/5minno breakdown, no flashover
Partial discharge 45kV≤10pC
Impulse voltage 200kV (10 times each positive and negative polarity)no breakdown, no flashover
Constant-voltage load cycle test in air (65kV, 95°C~100°C, each cycle heating 5h, cooling 3h, 30 cycles in total)no breakdown, no flashover
Constant-voltage load cycle test in water (65kV, 95°C~100°C, each cycle heating 5h, cooling 3h, 30 cycles in total)no breakdown, no flashover