Test itemTest requirements / Test results / Remarks
Power-frequency withstand voltage105 kV for 1 min, no flashover or breakdown / 105 kV for 1 min, no flashover or breakdown in any combined test specimen / Qualified
Partial discharge test39 kV, ≤10 pC / Discharge magnitude of each phase of combined test specimens ≤5 pC / Qualified
Load cycle test, 3 cycles5 h heating, 3 h cooling; during heating, conductor temperature 95 °C / Three load cycle tests completed as required by the standard / Evaluated by the following tests
Impulse voltage test, 1.2/50 μs, positive and negative polarity once each250 kV, one flashover allowed for positive and negative polarity but not counted in the total number of tests / 250 kV, positive and negative polarity 10 times each; no breakdown or flashover in any combined test specimen / Qualified
DC voltage test, negative polarity156 kV for 15 min, no flashover or breakdown / 156 kV for 15 min, no breakdown or flashover in any combined test specimen / Qualified
4 h power-frequency voltage test104 kV for 4 h, no flashover or breakdown / 104 kV for 4 h, no breakdown or flashover in any combined test specimen / Qualified