Power Series Products / Heat Shrink Cable Accessories
10kV heat-shrinkable termination
Model:

1 / 2

1

2
Description
1. Double ground wire process for heat-shrinkable termination heads of cross-linked cables. That is, the steel armor ground wire and the copper shield ground wire are separated, making cable preventive testing more reasonable. a. Measure the steel armor ground wire-to-ground resistance; if conductive, the inner lining layer has been damaged. Measure the copper shield ground wire-to-ground resistance; if conductive, both the inner and outer jackets of the cable have been damaged. c. A triangular cushion cone was developed for construction convenience. d. The finger shank has a tapered structure and never cracks.
Features
- 1. Double ground wire technique for heat-shrinkable terminal head of cross-linked cable. That is, the steel armor ground wire and the copper shield ground wire are separated, making cable pre-testing more reasonable. a. Measure the resistance between the steel armor ground wire and ground; continuity indicates that the inner lining layer has been damaged. Measure the resistance between the copper shield ground wire and ground; continuity indicates that both the inner and outer protective layers of the cable have been damaged. c. A triangular cushion cone was developed for construction convenience. d. The finger sleeve has a tapered structure and never cracks.
Specifications
1工频耐压试验 / AC 39kV,5min或DC 35kV,15min
2室温下局部放电试验 / 在15kV下组合试样无可检测放电
3高温下冲击电压试验,在θt2)下 / 95kV,正负极性冲击各10次不闪络,不击穿
4恒压负荷循环试验 / 在θt温度下和23kV下循环60次3)(空气中) / 在θt温度下和23kV下循环30次3)(空气中)和30次3)(水中)
5局部放电(在θt2)4)下和环境温度下t) / 在15kV下≤10pC
6短路热稳定(屏蔽5)) / 在电缆屏蔽的ISC下,短路2次,无可见损伤;
7短路热稳定(导体) / 升高到电缆导体的θSC下,短路2次,无可见损伤
8短路动稳定 / 在电缆屏蔽的Id下,短路1次,无可见损伤
9

1 / 2

1

2
Features
- 1. Double ground wire technique for heat-shrinkable terminal head of cross-linked cable. That is, the steel armor ground wire and the copper shield ground wire are separated, making cable pre-testing more reasonable. a. Measure the resistance between the steel armor ground wire and ground; continuity indicates that the inner lining layer has been damaged. Measure the resistance between the copper shield ground wire and ground; continuity indicates that both the inner and outer protective layers of the cable have been damaged. c. A triangular cushion cone was developed for construction convenience. d. The finger sleeve has a tapered structure and never cracks.
Specifications
1工频耐压试验 / AC 39kV,5min或DC 35kV,15min
2室温下局部放电试验 / 在15kV下组合试样无可检测放电