1Interface type / Type 2 / Type 3
2Interface type standard / EN50181 / EN50181
3Maximum operating voltage of equipment (kV) / 36 / 42
4Rated current (A) / 800 / 1250
5Power-frequency withstand test voltage (kV), 5min / 95 / 117
6Impulse withstand voltage (kV) / ±200 / ±200
7Partial discharge test 1.73U0 / ≤10 / ≤10
8Conductor rated temperature / Maximum temperature during normal operation (°C) / 90 / 90
9Rated short-circuit current 0.5 sec (kA) / 50 / 63
10Connection method with cable conductor / Crimping, detachable / Crimping, detachable
11Short-circuit current allowed through the earthing part / Not less than the selected cable / Not less than the selected cable
12Maximum insulation outer diameter the product accommodates (mm) / Max. 36 / Max. 57
240150-185 / 70-95 / 35-70 / 35 / 28-31
300240-300 / 120-150 / 95-120 / 50-70 / 30-33
400300-400 / 185-240 / 150-185 / 95-120 / 50-70 / 33-36
500500 / 300 / 240 / 150-185 / 95-120 / 36-39
630500 / 400 / 300 / 240-300 / 150-185 / 39-42
800800 / 54-59
Serial No.Name / Inner cone plug-in separable termination
Temperature during short circuit (°C)250 / 250
Voltage class (kV) Specification8.7/15 / 12/20 / 18/30 / 21/35 / 26/35 / 27.5 / Applicable insulation outer diameter (mm)
25-3516-19
50-7035 / 18-21
95-12050-95 / 21-24
150-18595-150 / 35-50 / 24-27
185-240150-185 / 95-120 / 33-36